RTA 460 User Manual

Browse online or download User Manual for Gateways/controllers RTA 460. RTA 460 User manual

  • Download
  • Add to my manuals
  • Print

Summary of Contents

Page 1 - QS460 User Manual

USER MANUALPut Bar Code Here69-2377—01QS460 User ManualGATEWAYS FOR TRANSFERRING DATA BETWEEN DEVICENET AND MODBUS RTU

Page 2 - 69-2377—01

Default IP Address – 192.168.0.100 Supported protocols The 460 Gateways connect devices with the following protocols: • ASCII RS232 • ASCII RS485

Page 3 - 460 User Manual

Default IP Address – 192.168.0.100 Chapter 2 Installing the 460 Gateway Before the 460 Gateway can transfer data, you need to do the following tasks

Page 4 - Revision history

Default IP Address – 192.168.0.100 Note: Only one RS232, RS485, or CAN port setting can be active per unit. For example, a unit cannot have two por

Page 5 - WARRANTY

Default IP Address – 192.168.0.100 2. Insert the power connector to the 460 gateway unit, and then plug the power cord into a power source. 3. Lau

Page 6

Default IP Address – 192.168.0.100 Note: If this is not the first time that this 460 Gateway has been configured, Figure 2-2 displays different mod

Page 7 - Table of Contents

Default IP Address – 192.168.0.100 Configuring the 460 Gateway The 460 Gateway always acts as at least two devices at a time (for example, a Modbu

Page 8 - Chapter 1 Introduction

Default IP Address – 192.168.0.100 Note: The Edit buttons are grayed out when the task applies to a different 460 Gateway version than you purchase

Page 9 - Specifications

Default IP Address – 192.168.0.100 Figure 2-5 Enable Modbus RTU Master configuration 3. Click on the Enabled? checkbox. The Module’s Detail opti

Page 10 - The 460 Gateway parts

Default IP Address – 192.168.0.100 Figure 2-8 Modbus RTU Master configuration details selected For Your Information: Familiar users can make all

Page 11 - Setting jumpers

Default IP Address – 192.168.0.100 8. For each new Device Buffer that should be enabled (1-32), click on the Add Remote Modbus RTU Slave button.

Page 13

Default IP Address – 192.168.0.100 Figure 2-11 Modbus RTU Master data selections 12. When you have finished editing device buffers for the Modbu

Page 14

Default IP Address – 192.168.0.100 Figure 2-12 Communication Module Configuration screen 2. Click on next to Modbus RTU Slave. The

Page 15 - Configuring the 460 Gateway

Default IP Address – 192.168.0.100 3. Click on the Enabled? checkbox. The Module’s Detail options expand when enabled. See Figure 2-14. Figure 2-

Page 16 - Modbus RTU Master

Default IP Address – 192.168.0.100 Figure 2-16 Modbus RTU configuration details selected For Your Information: Familiar users can make all desire

Page 17

Default IP Address – 192.168.0.100 ModbusTCPClientconfigurationIf your version of the 460 Gateway requires your gateway to act as a Modbus TCP C

Page 18 - Return to Main

Default IP Address – 192.168.0.100 Figure 2-19 Enable Modbus TCP Client configuration 3. Click on the Enabled? checkbox. The Module’s Detail op

Page 19

Default IP Address – 192.168.0.100 Figure 2-21 Modbus TCP Client Module Configuration 6. Click on next to the Client Module Configu

Page 20

Default IP Address – 192.168.0.100 Figure 2-23 Modbus TCP Client registers and program tags 9. Enter the Server IP Address and Unit ID. Select

Page 21 - Modbus RTU Slave

Default IP Address – 192.168.0.100 Figure 2-24 Modbus TCP Client data selections 11. When you have finished editing device buffers for the Modbus

Page 22

Default IP Address – 192.168.0.100 Figure 2-25 Communication Module Configuration screen 2. Click on next to Modbus TCP Server. Th

Page 23

 460 User Manual Gateways for transferring data between different protocols: BACnet/IP DeviceNet EtherNet/IP Modbus RTU Modbus TCP Seri

Page 24 - Modbus TCP Client

Default IP Address – 192.168.0.100 3. Click on the Enabled? checkbox. 4. Click on Save. For Your Information: Familiar users can make all desire

Page 25 - Enabled? checkbox

Default IP Address – 192.168.0.100 EtherNet/IPClientconfigurationIf your version of the 460 Gateway requires your gateway to act as an EtherNet/

Page 26

Default IP Address – 192.168.0.100 2. Click on next to EtherNet/IP Client. The Enabled? prompt displays. See Figure 2-29. Edit Figu

Page 27

Default IP Address – 192.168.0.100 5. Click on the button. The RTA 460 Gateway Main Page displays with a Client Mo

Page 28

Default IP Address – 192.168.0.100 Figure 2-32 External Device Configuration screen 7. To enable a Device Buffer, click on the Add Remote Etherne

Page 29 - Modbus TCP Server

Default IP Address – 192.168.0.100 1. Click on next to the Selected Communication Modules on the RTA 460 Gateway Main Page. See Figure

Page 30

Default IP Address – 192.168.0.100 Figure 2-35 Enable EtherNet/IP Server configuration 3. Click on the Enabled? checkbox. 4. Click on Save. F

Page 31

Default IP Address – 192.168.0.100 Figure 2-36 EtherNet/IP Server Configuration DeviceNetMasterconfigurationIf your version of the 460 Gateway

Page 32

Default IP Address – 192.168.0.100 Figure 2-37 Communication Module Configuration screen 2. Click on next to next to DeviceNet Mas

Page 33

Default IP Address – 192.168.0.100 Figure 2-39 DeviceNet Master configuration details 4. Select the appropriate communication options from the d

Page 34 - Edit in the Action column

Default IP Address – 192.168.0.100 Trademarks BACnet is a registered trademark of the American Society of Heating, Refrigerating and

Page 35 - Ethernet/IP Server

Default IP Address – 192.168.0.100 Figure 2-41 DeviceNet Master Client Module Configuration 7. Click on next to the Client Module C

Page 36

Default IP Address – 192.168.0.100 Buffer, click on the Add Remote DeviceNet Slave button and then edit that buffer’s settings. Figure 2-43 Devic

Page 37

Default IP Address – 192.168.0.100 Figure 2-44 Communication Module Configuration screen 2. Click on next to DeviceNet Slave. The

Page 38 - DeviceNet Master

Default IP Address – 192.168.0.100 Figure 2-45 Enable DeviceNet Slave configuration 3. Click on the Enabled? checkbox. The Module’s Detail optio

Page 39

Default IP Address – 192.168.0.100 Figure 2-47 DeviceNet Slave configuration details selected For Your Information: Familiar users can make all d

Page 40

Default IP Address – 192.168.0.100 BACnet/IPClientconfigurationIf your version of the 460 Gateway requires your gateway to act as a BACnet/IP Cli

Page 41

Default IP Address – 192.168.0.100 Figure 2-50 Enable BACnet/IP Client configuration 3. Click on the Enabled? checkbox. 4. Click on Save. Fo

Page 42 - DeviceNet Slave

Default IP Address – 192.168.0.100 Figure 2-51 BACnet/IP Client Module Configuration 6. Click on next to the Client Module Configur

Page 43

Default IP Address – 192.168.0.100 Figure 2-52 External Device Configuration screen 8. Enter the Device Address. Enter the registers and program

Page 44

Default IP Address – 192.168.0.100 Automation, Inc. (RTA) at 262.439.4999 or www.rtaautomation.com for more information about 460 Gateway configurat

Page 45 - BACnet Client

Default IP Address – 192.168.0.100 WARRANTY Equipment Warranty: All repair covered by this warranty must be done at Company's factory unless

Page 46

Default IP Address – 192.168.0.100 Figure 2-55 Enable BACnet/IP configuration 3. Click on the Enabled? checkbox. The Module’s Detail options exp

Page 47

Default IP Address – 192.168.0.100 Figure 2-57 BACnet/IP Server configuration details selected For Your Information: Familiar users can make all

Page 48

Default IP Address – 192.168.0.100 Serialconfiguration(Modules1and2)If your version of the 460 Gateway requires your gateway to act as a seria

Page 49 - BACnet Server

Default IP Address – 192.168.0.100 2. Click on next to next to Serial Module 1 (or Serial Module 2). The Enabled? prompt displays. Se

Page 50

Default IP Address – 192.168.0.100 Step Step Step 4c Step Step 4e Step 4f Figure 2-61 Serial Module configuration details a. Enter the maximum me

Page 51

Default IP Address – 192.168.0.100 Note: Only one RS232, RS485, or CAN port setting can be active per unit. For example, a unit cannot have two po

Page 52

Default IP Address – 192.168.0.100 6. Click on the button. The RTA 460 Gateway Main Page displays with a Client Mo

Page 53

Default IP Address – 192.168.0.100 Editing 460 Gateway Network Settings After the computer is connected to the 460 Gateway, use the following steps

Page 54

Default IP Address – 192.168.0.100 Step Step Step Step Figure 2-66 Network Setup screen 2. Enter the IP address that identifies the 460 Gateway

Page 55

Default IP Address – 192.168.0.100 Making Settings Take Effect Before any changes to the 460 Gateway’s configuration or network settings take effe

Page 56

Default IP Address – 192.168.0.100 What Other Limitations Are There? ANY IMPLIED WARRANTIES, INCLUDING WITHOUT LIMITATION THE IMPLIED WARRANTIES OF

Page 57

Default IP Address – 192.168.0.100 Figure 2-68 RTA 460 Utilities screen 2. Click on toward the top of the screen. A prompt disp

Page 58

Default IP Address – 192.168.0.100 Connecting cables Once the jumpers are set for the correct serial interfaces and the configuration and network

Page 59 - Making Settings Take Effect

Default IP Address – 192.168.0.100 Chapter 3 Troubleshooting After the 460 Gateway is set up, it should transmit and receive data correctly. However

Page 60

Default IP Address – 192.168.0.100 Note: If the web page does not display, check the following settings: The web page does not display when the com

Page 61 - Connecting cables

Default IP Address – 192.168.0.100 Figure 3-2 RTA 460 Device Summary and Status screen 6. Click or Press F5. The values on th

Page 62 - Chapter 3 Troubleshooting

Default IP Address – 192.168.0.100 Checking for solutions to common problems Use Table 3-1 to check for possible solutions to common problems. If

Page 63 - Status and Summary

Default IP Address – 192.168.0.100 460 Gateway User Manual Page 59 Problem Possible solutions The end of the data is being lost. You may be sen

Page 64 - Main Page

Default IP Address – 192.168.0.100 Chapter 4 General Procedures This chapter contains the following general information and procedures: • Configuri

Page 65

Default IP Address – 192.168.0.100 c. Click on Properties. d. Click Use the following IP address. e. Type in 192.168.0.10 (the last two digits a

Page 66

Default IP Address – 192.168.0.100 5. Click on The Utilities screen displays. See Figure 4-5. Figure 4-5 RTA 460 Utilities

Page 67 - Chapter 4 General Procedures

Default IP Address – 192.168.0.100 460 Gateway User Manual Page iv Table of Contents Chapter 1 Introduction ...

Page 68

Default IP Address – 192.168.0.100 7. Click Save. The Save As window displays. See Figure 4-7. Select a location to save the configuration file. 8.

Page 69 - Save Configuration to File

Default IP Address – 192.168.0.100 c. Click on Properties. d. Click Use the following IP address. e. Type in 192.168.0.10 (the last two digits a

Page 70 - Internet Protocol (TCP/IP)

Default IP Address – 192.168.0.100 5. Click on The Utilities screen displays. See Figure 4-9. Utilities Figure 4-9 RTA 460

Page 71

Default IP Address – 192.168.0.100 Changing IP or subnet addresses After the 460 Gateway is setup and installed, you can still change IP or subnet

Page 72 - Restore from File

Default IP Address – 192.168.0.100 Figure 4-10 Real Time Automation IPSetup screen 5. Click on Search Again. The 460 Gateway units on the network

Page 73 - TheIPSetup.exe

Default IP Address – 192.168.0.100 4. Launch the web browser. In the address window, enter http://192.168.0.100 Press Enter The Real Time Automati

Page 74

Default IP Address – 192.168.0.100 Step Step Step Step Figure 4-12 Network Setup screen 6. Enter the IP address that identifies the 460 Gateway

Page 75

Default IP Address – 192.168.0.100 Chapter 5 Panel mount dimensions Figure 5-1 shows the panel mount dimensions for the 460 Gateway. Figure 5-1 P

Page 76

Default IP Address – 192.168.0.100 460 Gateway User Manual Page 71

Page 77

69-2377—01

Page 78

Default IP Address – 192.168.0.100 Chapter 1 Introduction The 460 Gateway lets you control how to manipulate and control data, moving it bi-directio

Page 79

QS460 USER MANUALAutomation and Control SolutionsHoneywell International Inc. Honeywell Limited-Honeywell Limitée1985 Douglas Drive North 35 Dynamic D

Page 80 - ® U.S. Registered Trademark

Default IP Address – 192.168.0.100 Specifications Table 1-1 shows the specifications for the 460 Gateway. Table 1-1 460 Gateway specifications Item

Comments to this Manuals

No comments